Three-Phase Grounding Voltage Transformer (GVT), or Grounding Potential Transformer (GPT), for MV Indoor Applications
EGP-3DF, EGP-6DF
This ground voltage transformer (GVT), or ground potential transformer (GPT), is a three-phase medium-voltage (MV) potential transformer for indoor applications. With a fuse for each phase, this PT (VT) features epoxy-insulated coils and a five-legged (five-limbed) laminated core. This voltage transformer is used with measuring or monitoring instruments, or for ground-fault protection.
About the Product
The EGP-3(6)DF Series voltage transformers, designed for indoor applications, are three-phase “grounding potential transformers” (GPT), or “grounding voltage transformers” (GVT). On the primary side, each phase of the voltage transformer, or potential transformer, comes with a fuse to protect against overload and short circuit currents. This type of voltage transformer features coils insulated with Araldite® epoxy resin, as well as a five-legged laminated core. The primary rated voltage is 3300V (Y connection) or 6600V (Y connection). When the VT, or PT, is used in conjunction with measuring or monitoring instruments, the secondary rated voltage is 110V (Y connection).
This voltage transformer can also be used as a grounding voltage transformer for ground-fault protection. When any one phase of the primary side is grounded in an abnormal or accidental situation, the tertiary rated voltage is 0~190V (open-delta connection) or 0~110V (open-delta connection). The tertiary side produces and transmits a ground fault voltage signal to a monitoring device or ground relay, by which the VT (PT) achieves its monitoring purpose and the protection of equipment or individuals.
Specifications*
Standard | IEC or IEEE | |
Frequency | 50 or 60 Hz | |
System Voltage | Model: EGP-3DF | ≦ 3.6 kV |
Model: EGP-6DF | ≦ 7.2 kV | |
Connection | Y-Y-open△ | |
Primary Fuses | 3 |
Selection Table*
Model | Phase | Primary | Secondary Rated Voltage (V) | Tertiary | Burden / Accuracy | AC/BIL | Approx. |
EGP-3DF | 3 | 3300 | 110 | 190 (open△) or 110 (open△) | 3X200VA / 1.0CL + 3X200VA / 3P | 10/40 | 57 |
EGP-6DF | 3 | 6600 | 110 | 190 (open△) or 110 (open△) | 3X200VA / 1.0CL + 3X200VA / 3P | 20/60 | 57 |
- Download Documents
CIC Company Profile
Learn about our company: history, strengths, products, global locations, and our Advanced Electricity Lab.
【Product Brochure】Grounding Voltage Transformers, EGP-3(6)DF Series
Easy-to-print document, containing product description, specifications, and a selection table.
【Product Dimensions】Grounding Voltage Transformers, EGP-3(6)DF Series
Download PDF for basic drawing(s) and dimensions of this product. For more detailed information, please contact CIC.
CT & PT Selection Guide: How to Choose a Current Transformer or Potential Transformer
How to select, based on application and power system attributes, the primary and secondary currents, burden, accuracy, rated frequency, type (indoor vs. outdoor), insulation material, etc.
- Related Products
Single-Pole Voltage Transformers (Potential Transformers), or Three-Phase VT (PT) + GVT (GPT)
EPF-10CE, EPF-10DE, EPF-20SK, EPF-20SL, EPF-30DE
Voltage transformers from this series are indoor medium-voltage single-phase epoxy-resin-cast potential transformers suitable for 12kV, 24kV, and 36kV power systems. They are used in conjunction with measuring instruments for system monitoring and analysis or in combination with protective relays. Specific models can be equipped with a combination fuse assembly on the primary side. Additionally, models with a maximum thermal burden of 1000 VA can also function as a power source for circuit breaker operation, meaning they can serve as "control power transformers" or "control transformers," also known as CPT or CTR, or "industrial control transformers" or "machine tool transformers."
3.6 kV Current Transformer, Coil Molded
EW-3S
For measuring or monitoring instruments, this medium-voltage, indoor, coil molded current transformer is often used with the main panel or the motor control panel of a 3.6 kV (max.) power system. Insulated with Araldite® epoxy resin. Compact and easy to install.
Two-Core Coil Molded Current Transformer with Cut Cores, 3.6 kV
EW-3C
2-core (core type: cut-core), medium-voltage coil molded current transformer. Often used with the main panel or the motor control panel of a 3.6 kV (max.) power system. Good for protection. Suited to measuring and monitoring instruments. Araldite® epoxy resin.
3.6 kV / 7.2 kV Current Transformers (1-Core / 2-Core & Single-Ratio / Dual-Ratio Options)
CR-3(6)S-T Series
Intended for the main panel or the motor control panel of a 3.6/7.2 kV power system and designed to be used with measuring or monitoring instruments, or with protective relays. Each CT has a busbar terminal. Insulated with Araldite® epoxy resin.
3.6 kV Two-Core Epoxy-Cast Current Transformer
ER-3C
Offering a higher rated current ratio, this medium-voltage, two-core current transformer is suited to the main panel or the motor control panel of a 3.6 kV (max.) power system and can be used with measuring or monitoring instruments, or with protective relays. Araldite® epoxy resin.
Epoxy-Cast Window-Type Current Transformers for Indoor Application, 3.6 kV
CR-3S Series
2-core & single-core models. Indoor window-type current transformers for the main panel or motor control panel of a MV (≦ 3.6 kV) power system. Good for protection and appropriate for measuring and monitoring instruments. Araldite® epoxy resin.