Coil Molded Current Transformer with Cut Core, 12 kV
EW-10SH
Cut-core, medium-voltage, indoor-use, coil molded current transformer intended for a 12 kV (max.) power system and suited for measuring or monitoring instruments. Insulated with Araldite® epoxy resin.
Medium-Voltage Coil Molded Current Transformer
About the Product
Intended for a 12 kV (max.) power system and suited for measuring or monitoring instruments, this coil molded current transformer with a cut core is insulated with Araldite® epoxy resin. With a fine exterior, this medium-voltage current transformer for indoor use is compact and easy to install.
Specifications
- Standard: IEC or IEEE*
- Indoor application
- Coil molded
- High-grade silicon steel core
- Current Ratio: ≦ 400/5A
- System Voltage: ≦ 12 kV
- Frequency: 50 or 60 Hz
- AC/BIL: 28/75 kV
- Ith = 16 kA/1S
- Burden / Accuracy: 40VA/1.0
- Approx. Weight: 7 kg
Coil Molded Current Transformers (Selection Table)
Model | System | Primary | Secondary Current | Burden / Accuracy | Ith | AC/BIL | Approx. | Num. Of Cores | |
Core 1 | Core 2 | ||||||||
3.6 kV | 10~400A | 5A / 1A | - | 40VA/1.0 | 16 kA/1S | 10/40 | 5 | 1 | |
3.6 kV | 10~300A | 5A / 1A | 5A / 1A | 15VA/5P10 + 25VA/0.5 or 15VA/5P10+ 30VA/1.0 | 9 | 2 | |||
EW-10SH | 12 kV | 5~400A | 5A / 1A | - | 40VA/1.0 | 28/75 | 7 | 1 |
* Other standards and specifications available
- Download DocumentsRelated Products
CIC Company Profile
Learn about our company: history, strengths, products, global locations, and our Advanced Electricity Lab.
【Product Brochure】Coil Molded Current Transformers, EW Series
Including EW-3S, EW-3C, and EW-10SH. Production description, photos, and a selection table.
【Product Dimensions】Coil Molded Current Transformer with Cut Core, 12 kV (Model: EW-10SH)
Download PDF for basic drawing(s) and dimensions of this product. For more detailed information, please contact CIC.
CT & PT Selection Guide: How to Choose a Current Transformer or Potential Transformer
How to select, based on application and power system attributes, the primary and secondary currents, burden, accuracy, rated frequency, type (indoor vs. outdoor), insulation material, etc.