Burden for Current Transformer
WFY 47, 49 & 47-49
Burden for Current Transformer is mainly used for loading a CT during testing. Available in several structural designs for use in a variety of testing environments, this Burden for Current Transformer is compliant with IEC 60044-1 or ANSI/IEEE C57.13. Customer specifications can also be requested to satisfy different requirements.
About the Product
Burden for Current Transformer is mainly used for loading a CT during testing. Available in several structural designs for use in a variety of testing environments, this Burden for Current Transformer is compliant with IEC 60044-1 or ANSI/IEEE C57.13. Customer specifications can also be requested to satisfy different requirements.
Specifications
Standard | IEC60044-1 | ||
Models | WFY47 | WFY49 | WFY47-49 |
Rated Current | 1A | 5A | 1A & 5A |
Power Factor and Rated Burden | COSθ=0.8; 2.5~60 VA | ||
COSθ=1.0; 2.5~1.0VA | |||
Accuracy Class | ±3% | ||
Operation Range | 5% - 120% In | ||
Frequency | 50Hz, 60Hz |
Standard | ANSI/IEEE C57.13 | ||
Models | WFY47 | WFY49 | WFY47-49 |
Rated Current | 1A | 5A | 1A & 5A |
Power Factor and Rated Burden | COSθ=0.5; 25~200VA | ||
COSθ=0.9; 2.5~45VA | |||
Accuracy Class | ±3% | ||
Operation Range | 5% - 120% In | ||
Frequency | 50Hz, 60Hz | ||
|
- Download Documents
CIC Company Profile
Learn about our company: history, strengths, products, global locations, and our Advanced Electricity Lab.
【Product Brochure】Burden for Current Transformer
Color brochure with technical specifications, and other information.
- Related Products
Digital Tester (Comparator) for Instrument Transformers
WHES-1Cx
Digital Tester (Comparator) for Instrument Transformers is designed for the testing of ratio error and phase displacement of current transformers and voltage transformers (potential transformers).
Standard Potential Transformers (Voltage Transformers)
WHJB Series
WHJB Series Standard Potential Transformers are mainly used as reference PTs (VTs) in a variety of potential (voltage) transformer tests: error tests, characteristic tests, and so on.
Standard Current Transformers
WHLB Series
WHLB Series Standard Current Transformers are mainly used as reference CTs for current transformer measurements and tests: error tests, characteristic tests, and so on.
Burden for Potential Transformer (Voltage Transformer)
WFY 95
Burden for Potential Transformer is mainly used as the secondary load of a PT (VT) during testing. Available in several structural designs for use in various testing environments, this Burden for Potential Transformer is compliant with IEC 60044-1 or ANSI/IEEE C57.13. Customer specifications can also be requested to satisfy different requirements.
Instrument Transformer Testing System
WHES Series
WHES Series Instrument Transformer Testing System is designed to measure various properties of electromagnetic current transformers and potential transformers (voltage transformers).