Voltage Monitoring Sensor for Distribution Feeder Automation System (Outdoor Type, Pole-Mounted in Overhead Systems)
EDIO-F
Voltage Monitoring Sensor “Type EDIO-F” is designed for distribution feeder automation systems implemented for overhead distribution networks.
This voltage monitoring sensor can be used in a 25.5 kV (max.) overhead distribution network using distribution feeder automation system. This outdoor-type voltage monitor, to be pole-mounted in overhead systems, helps to provide voltage signals and data for monitoring and analysis purposes.
Voltage Monitoring Sensor Series for Distribution Feeder Automation System
Type | EDIO-F (this product) | |||
---|---|---|---|---|
Application | Indoor | Outdoor | Outdoor | |
Installation Location | Underground System Cables | SF6 Load Break Switch in Overhead Systems | Pole-Mounted in Overhead Systems | |
Rated Frequency (Hz) | 60 | |||
Rated Voltage (kV) | 10 ~ 25.5 | |||
Voltage Ratio (V) | 13200:5 | 13200:5 6600:2.5 | 6600:5 | |
Accuracy | ± 1% (Phase Displacement: ± 1.5°) | |||
Rated Power-Frequency Withstand Voltage (kV / 1 min.) | 50 | 60 | 28 (wet & dry) | |
Rated Impulse Withstand Voltage (kV) (1.2 / 50 μs) | 125 | 125 | 110 | |
Operating Temperature | - 10℃ ~ + 65℃ | N/A | - 10℃ ~ + 65℃ | |
Accessories (Optional) | Cable * | Yes | N/A | Yes |
Connector | Yes | N/A | Yes | |
Approx. Weight (kg) (without secondary lead wire) | 2.6 | 0.5 | 4.1 |
* Default cable specifications: AWG #21 outdoor cable (other specifications upon request).
Note: Further technical data, drawings, and dimensions available upon request.
- Download Documents
CIC Company Profile
Learn about our company: history, strengths, products, global locations, and our Advanced Electricity Lab.
- Related Products
Voltage Monitoring Sensor for Distribution Feeder Automation System (Indoor Type, for Underground Distribution Networks)
UV-5607
Voltage Monitoring Sensor “Type UV-5607” is designed for distribution feeder automation systems implemented for underground distribution networks.This voltage monitoring sensor can be used in a 25.5 kV (max.) underground distribution network using distribution feeder automation system. This indoor-type voltage monitor, installed at underground cables in such a system, helps to provide voltage signals and data for monitoring and analysis purposes.
Voltage Monitoring Sensor for Distribution Feeder Automation System (Outdoor Type, for use in SF6 Load Break Switch in Overhead Systems)
GDIO-C
Voltage Monitoring Sensor “Type GDIO-C” is designed for distribution feeder automation systems implemented for overhead distribution networks.This voltage monitoring sensor can be used in a 25.5 kV (max.) overhead distribution network using distribution feeder automation system. This outdoor-type voltage monitor, for installation in a SF6 load break switch in overhead systems, helps to provide voltage signals and data for monitoring and analysis purposes.
- Related News
18Jul 2023 High Demand Continues for Versatile Applications of Insulators and Bushings
The widespread use of epoxy resin insulators and bushings across various industries has led to a continuous increase in market demand. CIC not only provides commonly used epoxy resin products for medium-voltage distribution boards, such as support insulators and bushing plates for busbars, but also supplies a wide range of high-precision insulation components for various specialized applications.
Read More